Published: Građevinar 59 (2007) 1
Paper type: Professional paper
Download article (Croatian): PDF
Download article (English): n/a
Causes of collapse and remedy of steel-tank roof structures
Abstract
Results obtained during analysis of the causes of collapse of roof structures of steel tanks are presented, and solutions applied during remedial activities are described. Two heating oil tanks in Zagreb, whose steel structures partly caved in, were used as an example. It was established in the analysis that several errors were made in the initial design, and that these errors concern the completeness and accuracy of static computations for the load bearing structure (inadequate static system and inappropriate load combination).
Keywordssteel tank, remedy, roof structure, collapse, design, static system, load